Fire damper
Closes automatically on heat, usually when a fusible link melts, keeping fire from spreading through ductwork in rated walls and floors.
IBC Section 717
Answer a few questions about the duct and the wall, floor or ceiling it passes through. You get the fire, smoke, corridor or ceiling radiation damper requirement with the code section behind it.
Step 1
Use the edition your jurisdiction has adopted. State and local amendments often change damper rules, so check them too.
Each damper type answers a different hazard. The tool tells you which one the code requires for your penetration.
Closes automatically on heat, usually when a fusible link melts, keeping fire from spreading through ductwork in rated walls and floors.
Closes on a signal from smoke detection to stop smoke moving through ducts, for example at smoke barriers and rated corridors.
One damper that does both jobs, used where an opening needs both a fire damper and a smoke damper.
A fire and smoke damper tested to close against airflow, used where a duct passes through a corridor ceiling built like the corridor walls.
Protects duct openings and diffusers in the ceiling of a rated floor/ceiling or roof/ceiling assembly from radiant heat.
Ratings, testing standards and installation basics for each damper type
Pick the code edition, what passes through (a duct or an air transfer opening) and the assembly it crosses.
The tool asks only the questions that can change the answer for that assembly, including every exception in the code.
See each damper type as required, not required or prohibited, with the reason, the code section and what to specify.
The 2018, 2021 and 2024 International Building Code (Section 717 and the sections it references) and the matching International Mechanical Code sections for exhaust systems. You choose the edition at the start.
No. The tool explains what the model code requires for the situation you describe. Local amendments, project-specific conditions and the authority having jurisdiction can change the answer.
The mechanical code prohibits dampers in clothes dryer exhaust (IMC 504.2), commercial kitchen grease ducts (IMC 506.3.11) and hazardous exhaust (IMC 510.7.1 in 2018, 510.6.1 in 2021, 509.6.1 in 2024). Those ducts are protected with shafts, enclosures or other methods instead.
A wall can be a fire barrier and a horizontal exit, or a corridor wall and a smoke barrier. Run the tool once for each role and meet every requirement that comes out, for example a fire damper from one role and a smoke damper from the other (together a combination damper or separate dampers).
Yes. There is no account, no sign-up and nothing to install. Your answers stay in your browser and the page link; only the edition, the assembly and the type of result are counted for statistics.
For the rules behind the tool, read the guide to IBC Section 717: where each damper is required in fire walls, fire barriers, shafts, corridors, smoke barriers and floors, with the exceptions for each.