International Mechanical Code

Dampers in dryer, grease and hazardous exhaust ducts

The building code asks for dampers by assembly, but the mechanical code forbids them in some exhaust ducts. Where the two meet, the tool applies the mechanical code first and shows the protection that is used instead, or flags a conflict for the building official.

Rules last reviewed October 12, 2026. How the rules are checked

Where the rules are in each edition

Rule2024 IMC2021 IMC2018 IMC
Clothes dryer exhaust: no fire or combination dampersIMC 504.2IMC 504.2IMC 504.2
Common multistory dryer exhaust shaftsIMC 504.11IMC 504.11IMC 504.10
Common multistory kitchen exhaust shaftsIMC 505.5IMC 505.5IMC 505.5
Grease duct enclosuresIMC 506.3.11IMC 506.3.11IMC 506.3.11
Hazardous exhaust duct penetrationsIMC 509.6IMC 510.6IMC 510.7
Hazardous exhaust: no fire or smoke dampersIMC 509.6.1IMC 510.6.1IMC 510.7.1

Clothes dryer exhaust

Fire dampers, combination fire/smoke dampers and similar devices that obstruct the exhaust flow are prohibited in clothes dryer exhaust ducts (IMC 504.2). The backdraft damper at the outdoor termination is not affected. Where the building code would require a damper, the two codes conflict: build the duct to IMC 504.2 and confirm the protection with the building official.

Through a wall that would need a fire damper

Code conflict: building official approval neededAll three editions

The building code would require a damper here. IMC 504.2 lets a dryer duct pass through a rated assembly when the duct is galvanized steel or aluminum of the IMC 603.4 thickness and the assembly keeps its rating, but it prohibits dampers in the duct, so the two codes conflict. Reroute the duct if you can; otherwise build the duct to IMC 504.2, protect the penetration so the assembly keeps its rating, and confirm the protection with the building official.

Through a rated floor between two stories

Fire damper: prohibitedAll three editions

Fire damper: prohibited. Dampers are prohibited in dryer exhaust ducts, so use the code alternative: protect the duct as required by IBC 714.5. IBC 717.6.1, IBC 714.5, IMC 504.2

Full result in the tool: Dampers prohibited in this duct

Through a fire wall

Not permittedAll three editions

IBC 717.5.1 requires a fire damper at every duct through a fire wall, and the mechanical code prohibits fire dampers in clothes dryer exhaust. There is no code-prescribed way to take a dryer duct through a fire wall. Reroute the duct, or obtain approval of an alternative from the building official.

Into a common multistory dryer exhaust shaft

Fire damper: prohibited · Smoke damper: prohibitedAll three editions

Fire damper: prohibited. The mechanical code prohibits fire and combination fire/smoke dampers in this exhaust duct, and the building code waives them here. IBC 717.5.3 Exc. 5, IMC 504.2, IMC 504.11 (2021 and 2024), IMC 504.10 (2018)

Smoke damper: prohibited. Dampers that would block the exhaust flow are prohibited in this duct. IMC 504.2, IMC 504.11 (2021 and 2024), IMC 504.10 (2018)

Also: Protect the shaft penetrations with the subduct method: steel subducts at least 0.0187 inch thick extending 22 inches up inside the shaft, and an exhaust fan at the top of the shaft running continuously on power that meets IBC 909.11. IMC 607.5.5 Exc. 2, IMC 504.2, IMC 504.11 (2021 and 2024), IMC 504.10 (2018)

Full result in the tool: Dampers prohibited in this duct

Check this duct in the tool (2024 IBC)

Residential kitchen exhaust

Ordinary residential kitchen exhaust follows the normal damper rules, except in a common exhaust shaft that serves several stories, where the mechanical code allows only the backdraft damper.

Into a common multistory kitchen exhaust shaft

Fire damper: prohibited · Smoke damper: prohibitedAll three editions

Fire damper: prohibited. The mechanical code prohibits fire and combination fire/smoke dampers in this exhaust duct, and the building code waives them here. IBC 717.5.3 Exc. 5, IMC 505.5

Smoke damper: prohibited. Dampers that would block the exhaust flow are prohibited in this duct. IMC 505.5

Also: Protect the shaft penetrations with the subduct method: steel subducts at least 0.0187 inch thick extending 22 inches up inside the shaft, and an exhaust fan at the top of the shaft running continuously on power that meets IBC 909.11. IMC 607.5.5 Exc. 2, IMC 505.5

Full result in the tool: Dampers prohibited in this duct

Check this duct in the tool (2024 IBC)

Commercial kitchen grease ducts

Fire and smoke dampers must not be installed in commercial kitchen grease ducts (IMC 506.3.11). The duct is enclosed instead.

Through a rated wall, floor or ceiling

Duct enclosure required, no dampersAll three editions

A commercial kitchen grease duct that penetrates a ceiling, wall or floor must be enclosed all the way from where it penetrates to where it discharges, in a rated shaft, a field-applied enclosure or a factory-built enclosure. The enclosure is rated at least as high as the assembly penetrated and at least 1 hour, and serves only that grease duct. Fire and smoke dampers must not be installed in grease ducts.

Through a fire wall

Not permittedAll three editions

IBC 717.5.1 requires a fire damper at every duct through a fire wall, and the mechanical code prohibits dampers in grease ducts. There is no code-prescribed way to take a grease duct through a fire wall. Reroute the duct, or obtain approval of an alternative from the building official.

Check this duct in the tool (2024 IBC)

Hazardous exhaust

The mechanical code does not allow fire or smoke dampers in hazardous exhaust ducts (IMC 510.7.1 in 2018, 510.6.1 in 2021, 509.6.1 in 2024). Rated shafts and enclosures protect the walls and floors instead.

Through a rated wall

Duct enclosure required, no dampersAll three editions

Hazardous exhaust ducts that penetrate a fire-resistance-rated wall must be enclosed in fire-resistance-rated construction, built like a shaft, all the way from where it penetrates to where it discharges, unless the inside of the duct has an approved automatic fire suppression system. The enclosure must be rated at least as high as the highest-rated wall penetrated. Hazardous exhaust ducts may not have fire or smoke dampers.

Through a floor

Shaft enclosure requiredAll three editions

Hazardous exhaust ducts that penetrate a floor/ceiling assembly must be enclosed in a fire-resistance-rated shaft, whether or not the floor is rated. The duct may not have fire or smoke dampers.

Into its own shaft

Fire damper: prohibited · Smoke damper: prohibitedAll three editions

Fire damper: prohibited. The mechanical code does not allow fire dampers in hazardous exhaust ducts. IMC 509.6.1 (2024), IMC 510.6.1 (2021), IMC 510.7.1 (2018)

Smoke damper: prohibited. The mechanical code does not allow smoke dampers in hazardous exhaust ducts. IMC 509.6.1 (2024), IMC 510.6.1 (2021), IMC 510.7.1 (2018)

Also: Protect where the duct penetrates the shaft wall as a through-penetration under IBC 714.4.1 (tested assembly or listed firestop system). IMC 509.6.1.1 (2024), IBC 714.4.1, IMC 510.6.1.1 (2021), IMC 510.7.1.1 (2018)

Full result in the tool: Dampers prohibited in this duct

Check this duct in the tool (2024 IBC)

Common situations by edition

Common situations: the tool’s result in each edition
Situation2024 IBC2021 IBC2018 IBC
Clothes dryer exhaust through a 1-hour fire barrierCode conflict: building official approval neededCode conflict: building official approval neededCode conflict: building official approval needed
Clothes dryer exhaust through one rated floor, connecting two storiesDampers prohibited in this ductDampers prohibited in this ductDampers prohibited in this duct
Dryer exhaust into a common multistory dryer exhaust shaft, Group R, NFPA 13Dampers prohibited in this ductDampers prohibited in this ductDampers prohibited in this duct
Commercial kitchen grease duct through a fire barrierDuct enclosure required, no dampersDuct enclosure required, no dampersDuct enclosure required, no dampers
Hazardous exhaust duct through a fire barrierDuct enclosure required, no dampersDuct enclosure required, no dampersDuct enclosure required, no dampers
Hazardous exhaust duct through a floorShaft enclosure requiredShaft enclosure requiredShaft enclosure required

Select a result to open it in the tool with every answer filled in, including the conditions not listed here.