IBC 717.5.4

Fire dampers in fire partitions (IBC 717.5.4)

Fire partitions need fire dampers at ducts and air transfer openings, but several exceptions remove them, most often in sprinklered residential buildings.

Rated corridor walls are fire partitions too. Their extra exception for sprinklered buildings (717.5.4 Exception 1) and the corridor smoke damper rules are on the rated corridor page.

What counts as a fire partition (other than a corridor): Dwelling and sleeping unit separations, tenant separations in covered and open malls, elevator lobby separations and egress balcony separations. Since 2021 also some ambulatory care separations and vestibules.

Rules last reviewed October 12, 2026. How the rules are checked

Check your case in the tool (2024 IBC)Start the tool with the 2021 IBC · Start the tool with the 2018 IBC

When each damper is required

Every result the tool can give for a duct carrying heating, cooling or ventilation air, or an air transfer opening, through this assembly. Labels show where a result applies only to ducts, only to air transfer openings, or only in some editions.

Fire damper

  • Required

    In Group H, none of the 717.5.4 exceptions apply, so ducts and air transfer openings through a fire partition need a listed fire damper.

    IBC 717.5.4

  • Required

    Ducts and air transfer openings through a fire partition need a listed fire damper, and none of the exceptions apply.

    IBC 717.5.4

  • Not required

    Tenant separation walls in mall buildings that need not extend to the deck above do not need fire dampers.

    IBC 717.5.4 Exc. 2

  • Not requiredDucts only

    The fire partition is rated 1 hour or less, the building is fully sprinklered, and the duct is a ducted steel HVAC system that is continuous from the equipment to the outlets.

    IBC 717.5.4 Exc. 4

  • Not requiredDucts only

    The duct is a small steel duct above the ceiling with the required steel sleeve detail.

    IBC 717.5.4 Exc. 3

Also required

  • Flexible ducts and flexible air connectors may not pass through any fire-resistance-rated assembly, and flexible air connectors may not go through any wall, floor or ceiling at all. (ducts only) IBC 717.7
  • Where no damper is required, the duct penetration must still be firestopped so the wall keeps its rating (through-penetration or membrane-penetration protection). IBC 717.1.2, IBC 714.3 to 714.4.3

Common situations by edition

Common situations: the tool’s result in each edition
Situation2024 IBC2021 IBC2018 IBC
Duct through a 1-hour dwelling unit separation, NFPA 13R sprinklers, continuous steel ductworkNo damper requiredNo damper requiredNo damper required
Duct through a 1-hour fire partition, building not sprinkleredFire damper requiredFire damper requiredFire damper required
Small steel duct above the ceiling with the steel sleeve detail, building not sprinkleredNo damper requiredNo damper requiredNo damper required
Air transfer opening through a 1-hour fire partitionFire damper requiredFire damper requiredFire damper required
Duct through a mall tenant separation that is not required to reach the deckNo damper requiredNo damper requiredNo damper required
Duct through a fire partition next to a Group H areaFire damper requiredFire damper requiredFire damper required

Select a result to open it in the tool with every answer filled in, including the conditions not listed here.

Exceptions and conditions the tool checks

These are the questions the tool asks, in order, with the explanation it gives. Section numbers are shown for each edition where they differ.

Is either side of this wall a Group H (high-hazard) area?

Group H covers buildings or areas that store or use hazardous materials above set quantities.

What is the required fire-resistance rating of the assembly?

Use the rating the code requires for this wall or floor, shown on the life safety plans.

Is this a tenant separation wall in a covered or open mall building that is not required to extend to the floor or roof deck above?

IBC 717.5.4 Exc. 2

Is the building fully protected by an automatic sprinkler system?

  • Yes, NFPA 13 throughout. IBC 903.3.1.1
  • Yes, NFPA 13R throughout. IBC 903.3.1.2, used in some residential buildings
  • No, partial or NFPA 13D only.

Does the HVAC duct system meet all of these?

The exception applies only when every item is met:

  • It is a ducted HVAC system carrying supply, return or exhaust air
  • The ducts are sheet steel, No. 26 gage or thicker
  • The steel ductwork is continuous from the air handling equipment to the air outlets and inlets

IBC 717.5.4 Exc. 4

Does the duct meet all of these?

This exception covers small steel ducts above a ceiling with a specific sleeve detail.

The exception applies only when every item is met:

  • The duct is made of materials approved by the mechanical code
  • The duct is no larger than 100 square inches
  • The duct is steel at least 0.0217 inch thick
  • The duct has no openings that connect the corridor with adjacent rooms or spaces
  • The duct is installed above a ceiling
  • The duct does not end at a wall register in the rated wall
  • A steel sleeve at least 12 inches long and 0.060 inch thick is centered in the opening
  • The sleeve is fastened on both sides of the wall and on all four sides of the sleeve with steel angles at least 1-1/2 by 1-1/2 by 0.060 inch, fastened to the sleeve and to the wall with No. 10 screws
  • Mineral wool batting fills the gap between the sleeve and the wall all the way around

IBC 717.5.4 Exc. 3

Code changes that affect this assembly

Questions

Does a duct through a dwelling unit separation need a fire damper?

Not where the wall is rated 1 hour or less, the building is fully sprinklered and the steel HVAC ductwork is continuous.

Fire damper: not requiredAll three editions

Fire damper: not required. The fire partition is rated 1 hour or less, the building is fully sprinklered, and the duct is a ducted steel HVAC system that is continuous from the equipment to the outlets. IBC 717.5.4 Exc. 4

Also: Where no damper is required, the duct penetration must still be firestopped so the wall keeps its rating (through-penetration or membrane-penetration protection). IBC 717.1.2, IBC 714.3 to 714.4.3

Full result in the tool: No damper required

Do air transfer openings in fire partitions need fire dampers?

Yes, unless the wall is a mall tenant separation that does not have to reach the deck above. The other exceptions cover ducts only.

Fire damper: requiredAll three editions

Fire damper: required. Ducts and air transfer openings through a fire partition need a listed fire damper, and none of the exceptions apply. IBC 717.5.4

Full result in the tool: Fire damper required

What is the small duct exception?

A small steel duct above the ceiling, with a steel sleeve fastened with steel angles, needs no fire damper. Every item in the checklist below must be met.

Fire damper: not requiredAll three editions

Fire damper: not required. The duct is a small steel duct above the ceiling with the required steel sleeve detail. IBC 717.5.4 Exc. 3

Also: Where no damper is required, the duct penetration must still be firestopped so the wall keeps its rating (through-penetration or membrane-penetration protection). IBC 717.1.2, IBC 714.3 to 714.4.3

Full result in the tool: No damper required

Do the exceptions apply in Group H?

No.

Fire damper: requiredAll three editions

Fire damper: required. In Group H, none of the 717.5.4 exceptions apply, so ducts and air transfer openings through a fire partition need a listed fire damper. IBC 717.5.4

Full result in the tool: Fire damper required

Overview of IBC Section 717

Illustration