IBC 717.5.5

Smoke dampers in smoke barriers (IBC 717.5.5)

Every duct or air transfer opening through a smoke barrier needs a smoke damper unless one of two exceptions applies. A smoke barrier floor is also a rated floor, so the floor rules apply there too.

What counts as a smoke barrier: A wall or floor that divides a building into smoke compartments (common in hospitals), or encloses an area of refuge or an elevator lobby.

Rules last reviewed October 12, 2026. How the rules are checked

Check your case in the tool (2024 IBC)Start the tool with the 2021 IBC · Start the tool with the 2018 IBC

When each damper is required

Every result the tool can give for a duct carrying heating, cooling or ventilation air, or an air transfer opening, through this assembly. Labels show where a result applies only to ducts, only to air transfer openings, or only in some editions.

Fire damper

Smoke barrier floors only. A smoke barrier floor is also a rated floor, so these results come from the floor rules (IBC 717.6.1).

  • RequiredDucts only

    A duct through a rated floor connecting only two stories may skip the shaft if a listed fire damper is placed at the floor line.

    Or protect the duct as required by IBC 714.5 instead of the damper.

    IBC 717.6.1

  • Not requiredDucts only

    The duct meets every item of the exception (a small steel duct in a wall cavity serving one dwelling or sleeping unit and running continuously to the outside) and penetrates no more than three floors, so fire dampers are not needed at the floors. The exception is not available in Groups I-2 and I-3.

    IBC 717.6.1 Exception

Smoke damper

  • Required

    Ducts and air transfer openings through a smoke barrier need a listed smoke damper, and no exception applies.

    IBC 717.5.5

  • Not requiredDucts only

    The duct is steel and all of its openings are in one smoke compartment.

    IBC 717.5.5 Exc. 1

  • Not requiredDucts only

    Group I-2, Condition 2 smoke barrier with a fully ducted HVAC system and quick-response NFPA 13 sprinklers.

    IBC 717.5.5 Exc. 2

Ceiling radiation damper

Smoke barrier floors only. These results come from the ceiling penetration rules for rated floors (IBC 717.6.2).

  • RequiredDucts only

    Grille openings in the ceiling of a rated floor/ceiling or roof/ceiling assembly need a listed ceiling radiation damper.

    IBC 717.6.1 Exception item 5, IBC 717.6.2.1

  • RequiredDucts only

    Where a duct passes through the ceiling of the rated assembly, a listed ceiling radiation damper is required at the ceiling line.

    Or enclose the duct in a shaft that complies with IBC 713.

    IBC 717.6.2 item 2

  • RequiredAir transfer openings only

    A listed ceiling radiation damper is required at the ceiling line where an opening with no duct attached, such as a diffuser or grille, penetrates the ceiling of the rated assembly.

    IBC 717.6.2, IBC 717.6.2 item 3

  • Not required

    The rated assembly was tested and shown not to need ceiling radiation dampers.

    IBC 717.6.2 Exc. 1

  • Not requiredDucts only

    The exhaust or outdoor air duct is inside a wall cavity, protected as required by IBC 714.5.2, and does not run through any other dwelling unit or tenant space.

    IBC 717.6.2 Exc. 2

  • Not required

    The opening is protected by a duct outlet penetration system that was tested with the rated assembly.

    IBC 717.6.2 item 2 Exc. 3, IBC 717.6.2 item 3 Exc. 2

When a damper is not the answer

  • Shaft enclosure requiredDucts only

    A duct through two rated floors must be enclosed in a shaft. Only ducts connecting two stories may use a floor damper or firestop instead.

  • Shaft enclosure requiredDucts only

    A duct through three rated floors must be enclosed in a shaft. Only ducts connecting two stories may use a floor damper or firestop instead.

  • Shaft enclosure requiredDucts only

    A duct through four or more rated floors must be enclosed in a shaft. Only ducts connecting two stories may use a floor damper or firestop instead.

  • Shaft enclosure requiredAir transfer openings only

    An air transfer opening may not pass through a smoke barrier floor except inside a shaft enclosure.

  • Shaft enclosure requiredDucts only, 2018 and 2021 IBC

    In Group I-2 and I-3 occupancies, a duct through a rated floor must be enclosed in a shaft. The floor damper options do not apply.

Also required

  • Flexible ducts and flexible air connectors may not pass through any fire-resistance-rated assembly, and flexible air connectors may not go through any wall, floor or ceiling at all. (ducts only) IBC 717.7
  • Where no damper is required, protect the penetration with a through-penetration firestop system that is also tested for air leakage (an L rating, UL 1479). (ducts only) IBC 714.4, IBC 714.5.4

Common situations by edition

Common situations: the tool’s result in each edition
Situation2024 IBC2021 IBC2018 IBC
Duct with openings on both sides of a smoke barrier wallSmoke damper requiredSmoke damper requiredSmoke damper required
Steel duct with all of its openings in one smoke compartmentNo damper requiredNo damper requiredNo damper required
Hospital smoke barrier (Group I-2, Condition 2), fully ducted, quick-response sprinklersNo damper requiredNo damper requiredNo damper required
Air transfer opening through a smoke barrier wallSmoke damper requiredSmoke damper requiredSmoke damper required
Duct connecting two stories through a smoke barrier floorSmoke damper required, plus a fire damper or IBC 714.5 protection at the floor lineSmoke damper required, plus a fire damper or IBC 714.5 protection at the floor lineSmoke damper required, plus a fire damper or IBC 714.5 protection at the floor line
Same, where either story is Group I-2 or I-3Differs by editionSmoke damper required, plus a fire damper or IBC 714.5 protection at the floor lineShaft enclosure requiredShaft enclosure required

Select a result to open it in the tool with every answer filled in, including the conditions not listed here.

Exceptions and conditions the tool checks

These are the questions the tool asks, in order, with the explanation it gives. Section numbers are shown for each edition where they differ.

Is the smoke barrier a wall or a floor?

  • A wall.
  • A floor (horizontal smoke barrier). A floor smoke barrier is also a rated floor (a 1-hour rating applies; steel smoke barriers in Group I-3 are exempt), so the floor penetration rules apply too.

IBC 709.1

Is the duct steel, with all of its openings in a single smoke compartment?

If the duct only passes through the other compartment without any grilles or registers there, smoke cannot use it to cross the barrier. For an elevator lobby or area of refuge, answer yes only if every opening is inside the lobby or refuge area itself.

IBC 717.5.5 Exc. 1

Does the smoke barrier meet all of these?

The exception applies only when every item is met:

  • It is a smoke barrier required in a Group I-2, Condition 2 occupancy (hospital) by IBC 407.5
  • The HVAC system is fully ducted as described in IMC 603
  • The building has NFPA 13 sprinklers throughout with quick-response sprinklers

IBC 717.5.5 Exc. 2

How does the duct pass through the rated floor/ceiling?

  • Through the whole floor to another story. The duct passes through both the ceiling and the floor and connects stories.
  • Only into the ceiling below the floor. The duct enters the ceiling, for example to reach a diffuser or grille, but does not pass through the floor above.

IBC 717.6

Is either story the duct connects, or any part of this floor, a Group I-2 or I-3 occupancy?

Group I-2 includes hospitals and nursing homes. Group I-3 includes jails and detention centers. Include I-2 or I-3 areas in mixed-use buildings.

How many floors does the duct pass through outside of a shaft?

What is the required fire-resistance rating of the assembly?

Use the rating the code requires for this wall or floor, shown on the life safety plans.

Does the duct meet all of these?

This exception is common for small bathroom and dryer exhaust ducts in apartments and hotels.

The exception applies only when every item is met:

  • The duct is inside a wall cavity
  • The duct is steel at least 0.0187 inch thick (No. 26 gage)
  • The duct serves a single dwelling unit or sleeping unit and opens into no other
  • The duct runs continuously from that unit to the outside of the building
  • The duct is no larger than 4 inches nominal diameter
  • Together these ducts are no more than 100 sq in. per 100 sq ft of floor area
  • The gap around the duct is filled with materials that prevent flame and hot gases from igniting cotton waste under ASTM E119 or UL 263 fire exposure, with at least 0.01 inch of water positive pressure, for the rating of the floor

IBC 717.6.1 Exception

Does the duct have a grille opening in the ceiling of a rated floor/ceiling or roof/ceiling assembly?

IBC 717.6.1 Exception item 5

Was the rated floor/ceiling or roof/ceiling assembly tested (ASTM E119 or UL 263) in a way that shows it keeps its rating without ceiling radiation dampers?

Some listed assemblies, such as certain UL designs, allow unprotected duct openings. Check the listing for the assembly.

IBC 717.6.2 Exc. 1

Is it an exhaust or outdoor air duct inside a wall cavity, protected as required by IBC 714.5.2, that does not run through any other dwelling unit or tenant space?

Typical case: a bathroom or dryer exhaust duct rising inside a wall and entering the rated ceiling at the top plate on its way outside.

IBC 717.6.2 Exc. 2

Is the duct protected with a duct outlet penetration system that was tested with the rated assembly (ASTM E119 or UL 263)?

This is a specific outlet or boot system named in the listing of the rated floor/ceiling or roof/ceiling design. A generic fire-rated boot or duct wrap does not count. Answer yes only if the assembly listing names the system.

IBC 717.6.2 Exceptions

Code changes that affect this assembly

Questions

Does a smoke barrier wall need fire dampers?

Section 717.5.5 calls for smoke dampers only. If the same wall is also a fire barrier, run the fire barrier rules too and follow the stricter result.

Smoke damper: requiredAll three editions

Smoke damper: required. Ducts and air transfer openings through a smoke barrier need a listed smoke damper, and no exception applies. IBC 717.5.5

Full result in the tool: Smoke damper required

When is a smoke damper not required in a smoke barrier?

When the duct is steel with all of its openings in one smoke compartment, or in a Group I-2, Condition 2 smoke barrier with a fully ducted system and quick-response sprinklers.

Smoke damper: not requiredAll three editions

Smoke damper: not required. The duct is steel and all of its openings are in one smoke compartment. IBC 717.5.5 Exc. 1

Also: Where no damper is required, protect the penetration with a through-penetration firestop system that is also tested for air leakage (an L rating, UL 1479). IBC 714.4, IBC 714.5.4

Full result in the tool: No damper required

Do smoke barriers around elevator lobbies need smoke dampers?

Yes, unless an exception applies. The code exception refers to a steel duct with its openings in a single smoke compartment; the tool treats an enclosed elevator lobby or area of refuge as one compartment, so a steel duct with every opening inside the lobby or refuge area qualifies.

Smoke damper: requiredAll three editions

Smoke damper: required. Ducts and air transfer openings through a smoke barrier need a listed smoke damper, and no exception applies. IBC 717.5.5

Full result in the tool: Smoke damper required

What changed for smoke barrier floors in hospitals in 2024?

In 2024 a duct connecting two stories in Group I-2 or I-3 may use the floor damper option instead of a shaft.

Smoke damper required, plus a fire damper or IBC 714.5 protection at the floor line2024 IBC only

A duct through a rated floor connecting only two stories may skip the shaft if a listed fire damper is placed at the floor line. IBC 717.6.1

Ducts and air transfer openings through a smoke barrier need a listed smoke damper, and no exception applies. IBC 717.5.5

Shaft enclosure required2018 and 2021 IBC

In Group I-2 and I-3 occupancies, a duct through a rated floor must be enclosed in a shaft. The floor damper options do not apply.

Overview of IBC Section 717